MEANWELL 60W SINGLE OUTPUT SWITCHING POWER SUPPLY - LPV-60 SERIES - LPV-60-24
Specifications
Details
MEANWELL 60W SINGLE OUTPUT SWITCHING POWER SUPPLY - LPV-60 SERIES - LPV-60-24
-
LPV-60-24
Features
- Constant voltage design
- Universal AC input / Full range
- Withstand 300VAC surge input for 5 seconds
- Protections: Short circuit / Over load / Over voltage
- Cooling by free air convection
- Fully encapsulated with IP67 level
- Fully isolated plastic area
- Class II power unit, no FG
- Class 2 power unit
- Pass LPS
- Suitable for LED related fixture or appliance (such as LED Decorations or Advertisement devices)
- 100% full load burn-in test
- Low cost, high reliabaility
- 2 years warranty
GTIN CODE
SPECIFICATION
- Model : LPV-60-24
Output
- DC voltage : 24V
- Rated current : 2.5A
- Current accuracy : 0~2.5A
- Rated power : 60W
- Ripple & noise : 150mVp-p
- Voltage tolerance : ±5.0%
- Line regulation : ±1.0%
- Load regulation : ±2.0%
- Setup, Rise time : 500ms, 20ms / 230VAC 500ms, 20ms / 115VAC at full load(for 5~36V) ; 500ms, 30ms / 230VAC 500ms, 30ms / 115VAC at full load(for 48V)
- Hold up time : 50ms/230VAC 16ms/115VAC at full load
Input
- Voltage range : 90 ~ 264VAC 127 ~ 370VDC
- Frequency range : 47 ~ 63Hz
- EFFICIENCY (Typ.) : 86%
- AC current : 12V : 1.2A/115VAC 1A/230VAC
- Inrush current : COLD START 60A(twidth=525μs measured at 50% Ipeak) at 230VAC
- Max. No. of PSUs on 16A Circuit breaker : 3 units (circuit breaker of type B) / 6 units (circuit breaker of type C) at 230VAC
- Leakage current : 0.25mA / 240VAC
Protection
- Over load : 110 ~ 150% rated output power / Protection type : Hiccup mode, recovers automatically after fault condition is removed
- Over voltage : 27.6 ~ 32.4V / Protection type : Shut down o/p voltage, re-power on to recover
Environment
- Working temp. : -30 ~ +70℃ (Refer to ''Derating Curve'')
- Working humidity : 20 ~ 90% RH non-condensing
- Storage temp. humidity : -40 ~ +80℃, 10 ~ 95% RH
- Temp. coefficient : ±0.03%/℃ (0 ~ 50℃)
- Vibration : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
Safety & EMC
- Safety standards : UL879(except for LPV-60-5), UL1310(except for LPV-60-5), CSA C22.2 No. 207-M89(except for LPV-60-5, LPV-60-48), CAN/CSA C22.2 No. 223-M91(except for LPV-60-5,LPV-60-48), BIS IS15885(for LPV-60-12,LPV-60-24 only), EAC TP TC 004, IP67, IEC62368-1 , BS EN/EN62368-1 approved
- Withstand voltage : I/P-O/P:3KVAC
- Isolation resistance : I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
- EMC emission : Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2 Class A, BS EN/EN61000-3-3, EAC TP TC 020
- EMC immunity : Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, light industry level, EAC TP TC 020
Others
- MTBF : 5188.4K hrs min. Telcordia SR-332 (Bellcore) ; 732.1Khrs min. MIL-HDBK-217F (25℃)
- Dimension : 162.5*42.5*32mm (L*W*H)
- Packing : 0.4Kg; 32pcs/13.8Kg/0.63CUFT